R23

R23

Product code : 11

Used in very low temperature refrigeration systems, typically on the low stage of a multi-stage system. Has properties similar to R13 and can be used to replace R13 in an existing system.

R23 has higher discharge temperatures than R13, however, and equipment which is not designed to take this into account may suffer related failures.

Polyolester (POE) lubricants should be used, and it may still be necessary to charge hydrocarbon oil additives to ensure proper oil return. Check with OEM for specific oil and charging recommendations.

Part Number 5R23 9R23 20R23 70R23
Product Description 5lb Cylinder. 9lb Returnable CYL. 20lb Returnable CYL. 20lb Returnable CYL.